YJM-81時安達牌防觸電預(yù)警器
產(chǎn)品簡介:
YJM-81時安達牌防觸電語音預(yù)警器適用于適用于電力行業(yè)220V-500KV工作環(huán)境,六個電壓報警檔位可選,獨創(chuàng)的多段語音播報方式,實現(xiàn)真正的語音播報,無波段開關(guān)一鍵式操作使用簡單方便、具有自動檔位切換功能實現(xiàn)更高的安全防護,微安級靜態(tài)功耗,是電工特種作業(yè)人員極為有效地輔助安全用品。
產(chǎn)品適用范圍:
YJM-81適用于220/380V、10KV、35KV、110KV、220KV、500KV的工作環(huán)境,產(chǎn)品適合于發(fā)、變、送、配、農(nóng)電和在電氣設(shè)備上工作的人員使用,是電工特種作業(yè)人員的一種極為有效的輔助安全用品。
報警距離:
電壓等級
|
*最小安全距離(M)
|
報警距離
|
0.22/0.38KV
|
|
> 0.6M
|
10KV
|
0.70
|
0.7-1.2M
|
35KV
|
1.00
|
1.0-1.5M
|
110KV
|
1.50
|
1.5-2.5M
|
220KV
|
3.00
|
3.0-4.0M
|
500KV
|
5.00
|
6.0-9.0M
|
相關(guān)參數(shù):
1.報警方式:語音報警,有開機、關(guān)機、語音報警、電壓檔位播報、自檢、電量提示等多段語音提示。
2.支持電壓220/380V、10KV、35KV、110KV、220KV、500KV電壓,預(yù)警器為六檔電壓選擇,無波段開關(guān)、一鍵式電子切換電路安全可靠。
3.每隔4小時電壓檔位會自動切回較靈敏的10KV檔位,防止誤設(shè)置為高電壓檔位。
4.CR2450鈕扣電池供電,正常使用時間為1年,可更換電池
5.有自檢功能,可自檢當前檔位電壓。
6.預(yù)警器電池電量低會提示“電量低,請更換電池”,此時請更換電池。
7.數(shù)字集成電路、體積小、重量輕、靜態(tài)功耗微安級,工作性能穩(wěn)定可靠
8.預(yù)警器只對220V以上工頻50HZ-60HZ的電壓預(yù)警,電路通過數(shù)字濾波方式抗干擾 ,工作穩(wěn)定可靠。
9.有動畫學(xué)習視頻,可根據(jù)動畫視頻快速學(xué)習預(yù)警器使用方法。
聯(lián)系方式:
歡迎來電咨詢:18951949841(微信同號),固定電話:025-86883571 025-84930468
QQ:3167096730
User Manual of YJM-81 SHIANDAR Anti-Electric Shock Voice Warning Device
YJM-81 SHIANDAR anti-electric shock voice warning device is applicable to work environment of 220V/380V、10KV、35KV、110KV、220KV and 500KV. It is designed for operators of power generating, transforming, and distributing devices, as well as rural power equipments and electric devices, as an extremely useful supplementary safety devices for electricians and electrical operators.
Introduction of Performance
1. The warning distances are listed in the following table:
Voltage Level
|
Minimum Safety Distance (M)
|
Warning Distance
|
0.22/0.38KV
|
|
0.5-0.8M
|
10KV
|
0.70
|
0.7-1.2M
|
35KV
|
1.00
|
1.0-1.5M
|
110KV
|
1.50
|
1.5-2.5M
|
220KV
|
3.00
|
3.0-4.0M
|
500KV
|
5.00
|
6.0-9.0M
|
2.Press turn the band switch to suitable position before using the warning device, such as “35KV” and you will hear the voice prompt of “35KV”, which means the warning device is turned on and ready to work.
3.At the time of normal service, the warning device will switch to “10KV” automatically at every 4 hours for the purpose of preventing error working at high voltage level. “10KV” is the default voltage level of the warning device.
4.If danger voltage is detected, the warning device gives voice prompt of “Danger, electric shock! Keep away”. Follow the operation instructions now and take care.
5. Self-detection function: Press the button for 1.5s or longer, a self-detection voice prompt can be heard, such as “self-detection, 220KV”.
6.Replace the battery if voice prompt of “Low power, replace the battery please!”. Applicable battery: CR2450 button cell (3V).
Description on Usage
7. Please turn the band switch to suitable position before using the warning device. After the device is turned on, test the device with simulation inspection, Only if the device works normally in the simulation inspection, you can use it for work. If no voice prompt can be heard when starting the device for several times, it means the power of the battery has been used out and you need replace the used battery with new CR2450 button cell (3V) before you use it again.
8. When you check or repair aerial power lines, communication lines or electric device, and you are within the warning distance, if the warning device sounds continual alarms, it means you are too close to the lines and the electric equipments, so please be careful of your safety during work.
9.The warning device is applicable only to voltage of 220V or higher with working frequency of 50HZ-60HZ and relies on digital filtering to keep away from interference. It works stably and reliably. Attention: the warning device does not work for direct current, high frequency current or static electricity.
10.Before doing the test, please use, in the indoors environment, a 4M wire coated with insulating layer as an aerial power line to test the alarm distance for the voltage 220V. At the time of wiring, connecting the wire to the plug and insert into a 220V socket. Make sure the line is a 220V live line. Remember that if a power socket is used, it serves only to test whether the warning device can sound alarm but cannot be relied to determine the alarm distance. This alarm has passed strict test before leaving the factory.
11.Installation: Double-faced adhesive tape is designed on the back of the warning device, which makes it easy to glue the warning device to the safety helmet. Pull straight the antenna and fix the antenna on the safety helmet with a QC label. The safety helmet shown in the picture is for illustration only, with the lining removed.
Important: For your safety, please use the products properly ,do not make it collided, crashed, or pressed, Keep the products away from moisture or humidity since it is an electronic product and don’t disassemble or repair it unless you are authorized to do so.
One year warranty service (for non-man-made damage) is provided and the service life of the warning device is three years (cost of materials will be charged only outside the warranty period).